Toll Free: 1800 419 3356(7:00 am to 10:00 pm on All Days)

CAT 2725 kVA Diesel Generator C175 -16

Producing reliable power from 2500 kVA to 3100 kVA at 50 Hz, our 175-16 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100 per cent rated load in one step. The generator set is optimized for Low Fuel Consumption or Low Emissions.

Get a Quote

Overview

Producing reliable power from 2500 kVA to 3100 kVA at 50 Hz, our 175-16 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100 per cent rated load in one step. The generator set is optimized for Low Fuel Consumption or Low Emissions.

Generator Set Specifications

Minimum Rating
2500 ekW
Maximum Rating
3100 ekW

Electric Motor – 6030 AC/6030 AC FS

Voltage
220 - 13800 Volts
Frequency
60 Hz

Winch

Speed
1800 RPM

Generator Set Configurations

Emissions/Fuel Strategy
Low Fuel Consumption, U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 Nonroad Equivalent Emission Standards)

Engine

Engine Model
C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel
Bore
175 mm
Displacement
84.67 L
Stroke
220 mm
Aspiration
Turbo Aftercooled

Engine Specifications

Compression Ratio 50 Hz
16:7:1
Compression Ratio 60 Hz
15:3:1
Governor Type
ADEM™ A4
Fuel System
Common Rail

This site uses and sets "cookies" on your computer to help make this website better by keeping the site reliable and secure, personalizing content and ads, providing social media features, and analysing how the site is used. You can learn more about these cookies by clicking here. By clicking 'I Accept', you are agreeing to our use of cookies.